Section 7 Diagnostics
7-1
Section 7
Diagnostics
Service Diagnostic Chart
Symptom Possible Cause Corrective Action
Reach-In does not run Main ON/OFF switch is in the OFF
position
Set the switch to the ON position
Circuit breaker is tripped or fuse is
blown
Reset the breaker or replace the
fuse
Voltage is too low Correct the electrical service so
it does not vary more than
+/-10%
(Freezers Only)
(Freezers Only)
(Freezers Only)
High pressure cut-out (HPCO)
control has tripped
Condenser is dirty
Refrigerant was overcharged
High side refrigerant line or
component is plugged
Condenser fan motor is not
running
HPCO control is defective
Clearance around the unit is
insufficient
Condenser air is recirculating/
ambient temperature is
above specification
Expansion valve (TXV) does
not limit suction pressure
Liquid injection valve is
overfeeding
Defrost end/ fan delay
thermostat is defective
Clean the condenser
Evacuate and recharge the
system
Repair the line or replace
the drier, evacuate and
recharge the system
Check the motor
electrically, replace if
defective
Check the control, replace if
defective
See Clearance
Requirements on page 2-2
Make sure air temperature
at the condenser inlet is
within specification
Replace the TXV
See Liquid Injection Valve on
page 6-9
Check the control, replace if
defective
(Freezers Only)
Relay has de-energized
HPCO control has tripped
Coil on relay is defective
Automatic defrost time clock
is defective
Check the control
Measure the voltage at the
coil, replace if defective
Check the clock, replace if
defective