Section 7 Diagnostics
7-1
Section 7
Diagnostics
Service Diagnostic Chart
Symptom Possible Cause Corrective Action
Reach-In does not run Main ON/OFF switch is in the OFF
position
Set the switch to the ON position
Circuit breaker is tripped or fuse is
blown
Reset the breaker or replace the
fuse
Voltage is too low Correct the electrical service so
it does not vary more than
+/-10%
(Freezers Only)
(Freezers Only)
(Freezers Only)
High pressure cut-out (HPCO)
control has tripped
• Condenser is dirty
• Refrigerant was overcharged
• High side refrigerant line or
component is plugged
• Condenser fan motor is not
running
• HPCO control is defective
• Clearance around the unit is
insufficient
• Condenser air is recirculating/
ambient temperature is
above specification
• Expansion valve (TXV) does
not limit suction pressure
• Liquid injection valve is
overfeeding
• Defrost end/ fan delay
thermostat is defective
• Clean the condenser
• Evacuate and recharge the
system
• Repair the line or replace
the drier, evacuate and
recharge the system
• Check the motor
electrically, replace if
defective
• Check the control, replace if
defective
• See Clearance
Requirements on page 2-2
• Make sure air temperature
at the condenser inlet is
within specification
• Replace the TXV
• See Liquid Injection Valve on
page 6-9
• Check the control, replace if
defective
(Freezers Only)
Relay has de-energized
• HPCO control has tripped
• Coil on relay is defective
• Automatic defrost time clock
is defective
• Check the control
• Measure the voltage at the
coil, replace if defective
• Check the clock, replace if
defective